Estrich is the German word for screed: a mortar layer laid on a structural slab or on insulation, which levels the floor, spreads loads and carries the floor covering. The most common type is cement screed (CT). German screed work follows DIN 18560 and DIN EN 13813, and the CM test decides when the floor can be covered.
German screed terms and their English equivalents
| German term | English equivalent | Meaning |
|---|---|---|
| Estrich | Screed | Mortar layer that levels the floor and carries the covering |
| Zementestrich (CT) | Cement screed | Moisture-resistant, universal |
| Schnellestrich | Fast-drying screed | Ready for covering after days instead of weeks |
| Heizestrich | Heated screed | Floating screed over underfloor heating |
| Schwimmender Estrich | Floating screed | On insulation, with no firm contact to wall and slab |
| Verbundestrich | Bonded screed | Firmly bonded to the structural slab |
| Belegreife | Readiness for covering | Dry enough to lay the floor covering |
| Meterriss | Metre mark (datum line) | Wall mark one metre above the planned finished floor level |
More terms, each with its German word, are in the glossary.
How to read CT-C25-F4
The designation under DIN EN 13813 names the binder first: CT is cement screed. C25 is the compressive strength class with 25 N/mm², and F4 is the flexural strength class with 4 N/mm². For floating screed, flexural strength is the decisive figure.
The standards you will meet
- DIN 18560: screeds in building. Part 2 covers floating screed and heated screed, part 3 bonded screed, part 4 screed on a separating layer and part 7 heavy-duty screed.
- DIN EN 13813: screed materials and their designation, such as CT-C25-F4.
- DIN 18202: tolerances in building, which set how flat a screed area must be.
- DIN EN 1264-4: underfloor heating, including function heating.
Who does what on a German site
- The screed layer lays the insulation, edge insulation strip, separating layer and the screed itself.
- The heating engineer lays the pipes, pressure-tests them and runs the function heating.
- The floor layer carries out the CM test before covering.
Key numbers
| Item | Cement screed (CT) |
|---|---|
| Nominal thickness, floating (also the pipe cover for heated screed) | 45 mm (CT-F4) |
| Walkable | after about 3 days |
| Function heating, earliest | day 21 |
| Readiness for covering | 2.0 CM-% (heated 1.8) |
Function heating runs for 3 days at 20 to 25 °C, then 4 days at the maximum design temperature. It is not proof of readiness for covering. The timeline planner works out the dates, and heated screed explains the build-up.
What to send for a quotation
- Area in m², ideally per floor
- Planned build-up: insulation, screed thickness, underfloor heating yes or no
- Screed type, if already fixed
- Site location and floor level
- Desired date and the progress of the preceding trades
- Plans or photos, if available
IGRO GmbH works as a subcontractor for general contractors in Hamburg and the surrounding region. Details of the steps are on the page Process. To start, use the contact page.
As of 25 November 2026. The information is general technical guidance. It replaces neither the design nor the manufacturers' data for your project.